Home » Products » Heat Trace – CRG Heating Cable

Heat Trace – CRG Heating Cable

CRG® Heating Cables are designed for freeze protection of metal and plastic pipes, roof & gutter de-icing, frost heave prevention and floor warming applications. 150°F Maintain, 185°F Exposure, 120-277V operation, (3,5,8,10 w/ft) UL Approved, available from stock for fast shipment.

CRG®  Heating Cables are designed for freeze protection of metal and plastic pipes and tanks in building and construction market applications. CRG® Cables are also designed and approved for use in roof & gutter de-icing applications. The semiconductive polymer core changes its power output versus pipe temperature to optimize power usage and prevent overheating. The cables are designed for extended service life, are third-party tested and approved to strict industry standards for building and construction market applications. Cables are available from stock for same-day shipment.

APPLICATIONS | Freeze Protection; Roof & Gutter De-Icing; Frost Heave Prevention; Floor Warming; Fire Equipment Freeze Protection; Heat Loss replacement

TEMP RANGE | -40-185F

  • Self-Regulating Power Output
  • Continuous Maintenance Temperature
    • 150°F (65°C) Max
  • Maximum Exposure Temperature
    • 185°F (85°C) Max
  • Output Wattage (pipe application)
    • 3, 5, 8, & 10 W/FT @ 50°F
    • 10, 16, 26, & 33 W/M @ 10°C
  • Output Wattage (roof and gutter)
    • 12 W/FT in snow/ice (32°F)
  • Supply Voltage
    • 120, 208-277 VAC
  • Size = 1/2” W x 1/4” H
  • Minimum Bend Radius = 1 1/8”
  • Minimum Install Temperature
    • -40°F (-40°C)
  • Cut to Length and terminate in the field
  • Can be overlapped without burnout