Heat Trace – HSRX
HSRX Heating Cables are designed for freeze protection and process temperature maintenance of metal pipes and tanks. HSRX cables provide temperature maintenance to 300°F and withstand temperature exposure to 482°F.
HSRX is available from stock in 5,10,15,20 watts/ft, 120 volt or 208-277 volt models. Self-regulating construction allows for maximum flexibility, cutting to length in the field, field termination, and overlap without burnout. Approved for ordinary and hazardous area use with approved QMark/Berko connection and termination kits.

Additional Information
Max. Intermittent Exposure Temp.
- 482°F (250°C)
Max. Maintain or Continuous Exposure Temp.
- 300°F (150°C)
Supply Voltage
- 120V or 208 – 277V
Output Wattage
- 5, 10, 15, 20W/ft @50°F (16, 33, 49, 66W/m @10°C)
Bus wire
- 16 AWG
Min. Bending Radius
- 1.2″(30mm) @ 70°F (20°C), 2.0″(50mm) @ -40°F (-40°C)
Min. Installation Temperature
- -76°F (-60°C)
Min. Start-up Temperature
- -40°F (-40°C)
Max. Circuit Breaker Size
- 50A
Outer Jacket Color
- Red
Heating Cable Dimensions (Nominal)
- 0.520 x 0.178″ (13.2×4.5mm)
Heating Cable Weight
- 0.296 lb/ft (0.134kg/m)