BPH SERIES - PLENUM-RATED UNIT HEATER, CONCEALED SPACE USE - ZERO CLEARANCE

IDEAL SPACES | Concealed Areas; Concession Stands; Bathrooms; Plenum Areas; Entrance Ways

COLORS | Neutral Gray

TEMP RANGE | 40°-90° F                      

CFM | 350-1000

DIMENSIONS | Varies (see specifications)

 

  • Plenum-rated approved for installations in concealed spaces (between finished ceiling and drop ceiling, plenum space, or inside a plenum). It may be installed in areas that are not readily accessible and may be installed for freeze protection
  • Compact size, zero clearance, design for horizontal installation
  • Connects to duct work for home extensions – eliminates running duct work to HVAC saving money and time
  • High limit thermal cutout - automatic reset
  • Built-in disconnect switch
  • Fan-only option
  • Timed blower on/off delay
  • External 24Vthermostat control (not included)
  • PSC-type 2-speed motor (ex. 480V models)
  • Multiple heat rise selection
  • 20-gauge all powder coated steel construction
  • Acoustic fiberglass insulation
  • Single point power connection
  • Heavy-duty steel finned heating element
  • Quiet, efficient, forward-curved centrifugal blower
See more HeatersSee more Berko products

Additional Information

CATALOG NUMBER UPC - 6-85360 PHASE KILOWATTS VOLTS LOW SPEED AMPS* HIGH SPEED CFM** CFM LBS. H x W x L
BPH138124 14993 6 1 3.0 208 15.32 350 400 49 12.5”x19.5”x24
BPH132124 15009 3 1 3.0 240 13.40 350 400 49 12.5”x19.5”x24
BPH137124 15015 4 1 3.0 277 11.63 350 400 49 12.5”x19.5”x24
BPH138324 14995 0 3 3.0 208 9.23 350 400 49 12.5”x19.5”x24
BPH132324 15011 6 3 3.0 240 8.12 350 400 49 12.5”x19.5”x24
BPH134324 15013 0 3 3.0 480 4.11 350 400 49 12.5”x19.5”x24
BPH158124 15005 5 1 5.0 208 24.94 350 400 49 12.5”x19.5”x24”
BPH152124 14997 4 1 5.0 240 21.73 350 400 49 12.5”x19.5”x24”
BPH157124 15003 1 1 5.0 277 18.85 350 400 49 12.5”x19.5”x24”
BPH158324 15007 9 3 5.0 208 14.78 350 400 49 12.5”x19.5”x24”
BPH152324 14999 8 3 5.0 240 12.93 350 400 49 12.5”x19.5”x24”
BPH154324 15001 7 3 5.0 480 6.51 350 400 49 12.5”x19.5”x24”
BPH158124L 15105 2 1 5.0 208 24.94 850 1000 49 18”x18”x35.5
BPH152124L 15097 0 1 5.0 240 21.73 850 1000 49 18”x18”x35.5
BPH157124L 15103 8 1 5.0 277 18.85 850 1000 49 18”x18”x35.5
BPH158324L 15107 6 3 5.0 208 14.78 850 1000 49 18”x18”x35.5
BPH152324L 15099 4 3 5.0 240 12.93 850 1000 49 18”x18”x35.5
BPH154324L 15101 4 3 5.0 480 6.51 850 1000 49 18”x18”x35.5
BPH1758124 15025 3 1 7.5 208 38.12 850 1000 69 18”x18”x35.5
BPH1752124 15017 8 1 7.5 240 33.31 850 1000 69 18”x18”x35.5
BPH1757124 15023 9 1 7.5 277 28.91 850 1000 69 18”x18”x35.5
BPH1758324 15027 7 3 7.5 208 22.88 850 1000 69 18”x18”x35.5
BPH1752324 15019 2 3 7.5 240 20.10 850 1000 69 18”x18”x35.5
BPH1754324 15021 5 3 7.5 480 10.16 850 1000 69 18”x18”x35.5
BPH1102124 15029 1 1 10.0 240 43.73 850 1000 69 18”x18”x35.5”
BPH1107124 15035 2 1 10.0 277 37.93 850 1000 69 18”x18”x35.5”
BPH2102124 15109 0 1 10.0 240 43.73 850 1000 69 18”x18”x35.5”
BPH2107124 15115 1 1 10.0 277 37.93 850 1000 69 18”x18”x35.5”
BPH1108324 15037 6 3 10.0 208 29.82 850   69 18”x18”x35.5”
BPH1102324 15031 4 3 10.0 240 26.12 850   69 18”x18”x35.5”
BPH1104324 15033 8 3 10.0 480 13.17 850   69 18”x18”x35.5”
BPH2108324 15117 5 3 10.0 208 29.82 850 1000 69 18”x18”x35.5”
BPH2102324 15111 3 3 10.0 240 26.12 850 1000 69 18”x18”x35.5”
BPH2104324 15113 7 3 10.0 480 13.17 850 1000 69 18”x18”x35.5”
BPH1158324 15043 7 3 15.0 208 43.90 850 1000 69 18”x18”x35.5”
BPH1152324 15039 0 3 15.0 240 38.14 850 1000 69 18”x18”x35.5”
BPH1154324 15041 3 3 15.0 480 19.18 850 1000 69 18”x18”x35.5”
BPH2152324 15119 9 3 15.0 240 38.14 850 1000 69 18”x18”x35.5”
BPH2154324 15121 2 3 15.0 480 19.18 850 1000 69 18”x18”x35.5”
*Total Amps including Resistive and Inductive loads. **Low and High speed fan operation is determined during installation of thermostat set up † Tested @0.2” S.P.
** Low speed fan operation not available on 480V models.